Vulcain/Honeywell Analytics Gas Monitors

Explosion Proof Oxygen, Toxic & Combustible Gas Monitors

Sensepoint XCD TransmitterThe Sensepoint XCD transmitter for commercial applications provides comprehensive monitoring of flammable, toxic and oxygen gas hazards in potentially explosive atmospheres, indoors and outdoors — and is marked by installation ease and flexibility, user-friendly operation and cost-effective gas monitoring.

Three different types of the XCD transmitter are available for use with three different families of sensors. The mV type transmitter is for use with the mV family of XCD sensors including catalytic bead sensors to detect flammable gases in the range 0-100%LEL. The Electro Chemical (EC) type transmitter is for use with the EC family of XCD sensors including carbon monoxide (CO), hydrogen sulfide, (H2S), hydrogen (H2) and nitrogen dioxide (NO2). The oxygen transmitter is for use with the oxygen (O2) XCD sensors.

SENSEPOINT XCD SENSOR FAMILIES, GASES AND RANGES
Sensor Family mV Gas User Selectable Full Scale Range Default Range Range Increments Selectable Cal Gas Range Default Cal Point
Catalytic Bead Sensors 30 to 70% of selected full scale range
Flammable 1-8• 20-100% LEL 100% LEL 10% LEL 50% LEL
Infrared Sensors
Methane 20-100% LEL 100% LEL 10% LEL 50% LEL
Propane 20-100% LEL 100% LEL 10%LEL 50% LEL
Carbon Dioxide 2%Vol. 2% Vol. 2% Vol. 1% Vol.
EC Electrochemical Sensors
Hydrogen Sulfide 10-100 ppm 50.0 ppm 0.1ppm 10 ppm
Carbon Monoxide 100-1,000 ppm 300 ppm 100 ppm 100 ppm
Hydrogen 1,000 ppm only 1,000 ppm n/a 500 ppm
Nitrogen Dioxide 10-50 ppm 10 ppm 5 ppm 5 ppm
O2 Oxygen 25% Vol. only 25% Vol. n/a 20.9% Vol. (Fixed) 20.9% Vol.

Setra Room Condition Monitoring

Gas Detection Controller

Control and monitor for toxic and combustible gases and oxygen hazards locally or through a Building Automation System network while reducing cost of installation and ownership of a gas detection system.

Gas detection controller

User Friendly

  • Zero Maintenance
  • Automatic, quick self test and warm-up
  • Continuous alphanumeric display

Inexpensive and reliable

  • Lowers installation costs by using only two pairs of wires to connect up to 96 transmitters
  • Allows for up to 126 zoning groups which can extend fan and relay life
  • Manages up to 768 events with programming latching alarms

Flexible Operation

  • Modbus compatible; with BACnet/IP and datalogging options
  • Transmitters able to detect different gases
  • Expands to handle up to 96 transmitters or relay modules
  • Programmable time delays
  • Integrated time clock enables scheduling of system operations
  • Available in heavy duty Industrial enclosure
  • Full array of visual indicators and integrated 65dBA alarm levels
ORDER # DESCRIPTION
VA301C Controller, Plastic Enclosure
VA301C-DLC Controller with Datalogger, Plastic Enclosure
VA301C-DLC-BIP Controller, Datalogger, BACnetI/P Output, Enclosure
301C-DLC-W Wireless Controller with Datalogger, Plastic Enclosure
301C-DLC-BIP-W Wireless Controller, Datalogger,BACnet/IP Output, Plastic
AIRALERT-96D Controller with Datalogger, Industrial Enclosure
AIRALERT-96D-BIP Controller, Datalogger,BACnet/IP Output, Industrial Encl.
VA301R8 Relay Module with 8 Relays
301R8-W Wireless Relay Module with 8 Relays
301R8-W-F Wireless Relay Module with 8 Failsafe Relays
VA301AP Annunciator Panel for VA301C
VA301ADI
Analog Digital Input Converter (4-20mA to Modbus RS-485)
VA420I Digital Output Analog Converter (Modbus RS-485 to 4-20mA)
Part # Description  
301R8-W Wireless Relay Module with 8 Relays Call... Add to Order
VA301R8 Relay Module with 8 Relays Call... Add to Order
VA301AP Annunciator Panel for VA301C Call... Add to Order
VA301ADI Analog Digital Input Converter (4-20mA to Modbus RS-485) Call... Add to Order
301R8-W-F Wireless Relay Module with 8 Failsafe Relays Call... Add to Order
VA301C Controller, Plastic Enclosure Call... Add to Order
VA420I Digital Output Analog Converter (Modbus RS-485 to 4-20mA) Call... Add to Order

Refrigerant, Toxic & Combustible Gas Controller

The 301EM-20 acts as a controller for up to 20 remote sensors and suits a variety of gas detection system solutions for Mechanical rooms.

Particularly configured to meet ASHRAE 15, B-52 and International Mechanical Code requirements, the 301EM-20 is commonly used to optimize gas detection in mechanical and chiller rooms. A full complement of sensors (including toxic, oxygen, combustible gases and a full line of refrigerant sensors) horns, strobes and remote panels provide added flexibility to suit a variety of gas detection system solutions.

Refrigerant toxic and combustible gas controller

SENSOR TYPE
Gases Detected Detection Range Infrared Refrigerant Gas Sensors

Refrigerant

301IRFS

R11, R12, R22, R13B1, R123, R125, R134A, R227, R245A, R404A, R407C, R410A, R507A, R508B 0-1000 ppm Order # Gas Order # Gas

Explosion-Proof

S301D2

Carbon Monoxide (CO) 0-250 ppm VA301IRFSR11 R11 VA301IRFSR245A R245A
Chlorine (Cl2) 0-15 ppm VA301IRFSR13B1 R13B1 VA301IRFSR404A R404A
Nitrogen Dioxide (NO2) 0-10 ppm VA301IRFSR22 R22 VA301IRFSR407C R407C
Hydrogen Sulfide (H2S) 0-50 ppm VA301IRFSR123 R123 VA301IRFSR410A R410A
Sulfur Dioxide (SO2) 0-10 ppm VA301IRFSR125 R125 VA301IRFSR507A R507A
Oxygen (O2) 0-25% VA301IRFSR134A R134A VA301IRFSR508B R508B


VA301IRFSR227 R227

Combustibles 0-100% LEL
S301D2CL2 C12 S301D2CO CO
S301D2H2S H2S S301D2NO2 NO2
S301D2O2 O2 S301D2SO2

SO2

Part # Desc  
VA301EM-RFSA-20 Controller w/three 24vdc Outputs, four Relays, four 4-20mA, Strobe Light & Horn, Network Call... Add to Order
VA301EM-20 Controller w/three 24vdc Outputs, four Relays, four 4-20mA, Network Call... Add to Order
VA301EMRP-20 Remote Panel, four Relays, Strobe Light Call... Add to Order

E3Point Toxic & Combustible Gas Monitor

E3Point toxic and combustible gas monitorThe E3Point Gas Monitor is available in standalone, standalone with remote (dual gas mode) or network versions. It connects to any analog or digital system. It works with virtually any Building Automation System including BACnet and Modbus. This monitor connects to wired systems or a hybrid wired/wireless system (via 301CW wireless controller) Detects CO, NO2, O2, H2, H2S, CH4, & C3H8 with factory calibrated sensor cartridges.

MAIN UNIT -WALL MOUNT VERSION
Stand-Alone, Single Gas Monitor
ORDER # DESCRIPTION
E3SASCO E3Point with CO Sensor, 4-20mA, 24VAC/DC
E3SA E3Point without Sensor, 4-20 mA, 24VAC/DC
E3SAHSCO E3Point with CO Sensor, 4-20mA, 120VAC/DC
E3SAH E3Point without Sensor, 4-20 mA, 120VAC/DC
Network, Single Gas Monitor
ORDER # DESCRIPTION
E3SBSCO E3Point with CO Sensor, BACnet, 24VAC/DC
E3SB E3Point without Sensor, BACnet, 24VAC/DC
E3SMSCO E3Point with CO Sensor, Modbus, 24VAC/DC
E3SM E3Point without Sensor, Modbus, 24VAC/DC
MAIN UNIT -DUCT MOUNT VERSION
Stand-Alone, Single Gas Monitor
ORDER # DESCRIPTION
E3DASCO E3Point with CO Sensor, 4-20mA, 24VAC/DC
E3DA E3Point without Sensor, 4-20 mA, 24VAC/DC
Network, Single Gas Monitor
ORDER # DESCRIPTION
E3DMSCO E3Point with CO Sensor, Modbus, 24VAC/DC
E3DM E3Point without Sensor, Modbus, 24VAC/DC

Gas Sensors and Cartridges are required when ordering the E3Point Monitor. When ordering, specify which gases will be monitored and our sales technicians will select the correct sensor. Available sensors are; Carbon Monoxide (CO), Nitrogen Dioxide (NO2), Hydrogen Sulfide (H2S), Hydrogen (H2), Oxygen (O2), Methane (CH4), Propane (C3H8).