LonWorks Analog-Pneumatic Serial Transducer
LonWorks Input—Pneumatic Output LonWorks Node
(Click to enlarge chart)
The PNP is a LonWorks compatible pneumatic output node. It uses the LonTalk network protocol and an FTT-10A free topology bus transceiver.
Specifications:
- Power: 24Vac/dc, 150mA max.
- Connection: 1/4'' brass barb
- Inputs: Twisted Pair LonTalk
- Mount: 2.25'' Snap Track (included)
- Output: 0–15 psi
1 Analog Input—Floating Output LonWorks Node
(Click to enlarge chart)
The LMP is a floating point output LonWorks node. It allows the user to read the analog input and control the floating point output. The analog input allows a motor position feedback signal to be monitored by the LonWorks network. The feedback input is jumper selectable for 0–5Vdc, 0–10Vdc, 0–20mA or 10K ohm thermistor range. In addition, three connections accept a resistance input from control motor auxiliary potentiometers.
Specifications:
- Power: 24Vac/dc, 180mA max.
- Mount: 2.25'' Snap Track (included)
- Inputs: Twisted Pair LonTalk
- Output: SPDT, 2A Floating