Fieldpiece Accessory Heads

Fieldpiece Manometer Head

Measures gas pressure and has resolution low enough for static pressure.

  • Maximum 20” WC for gas pressure
  • 0.01” WC resolution for static pressure
  • Manual zero-set for comparing two pressures
  • Includes tube and adapter for pressure measurement
  • Auto-off can be disabled for data logging

Fieldpiece Current Clamp

Measures AC or DC current up to 600A.

  • Current range: 1A to 600A AC or DC
  • ACA accuracy@60Hz, <400A:+/- (2%rdg+2A)
  • ACA accuracy@60Hz, >400A:+/- (6%rdg+2A)
  • Jaw opening 1.18" (30mm)

Fieldpiece Carbon Dioxide Head

The first step in addressing IAQ. Also can be used to determine outside air mix.

  • Sensing range: 0-2000 PPM
  • Accuracy: +/-75 PPM (0-1500 PPM); +/-5% reading (> 1500 PPM)
  • Sensing method: Non-dispersive Infrared (NDIR)
  • Operating temperature range: 32°F to+120°F
  • Gas sampling mode: diffusion
  • Repeatability: +/-9 PPM

Fieldpiece Voltage Head

Records voltage using DL2 data logger.

  • Accuracy: DC: +/- (0.5%rdg+1dgt); AC: +/-(1.0%rdg+4dgts)
  • Max Voltage: 600V AC or DC
  • Input impedance: 1Mohm
  • Standard test leads plug in top

Part # Accessory Heads  
ACD1 Carbon Dioxide Head Call... Add to Order
ACDC6 Current Clamp Call... Add to Order
AMN2 Manometer Head Call... Add to Order
AVH1 Voltage Head Call... Add to Order